JGF (245-550) kV

CURRENT TRANSFORMERS | OUTDOOR OPERATION

  • SF6-gas insulated
  • Primary winding changeover
  • Pressure release by using a metal burst-disc
  • Fine-graded foil bushing
  • Only silicone insulator available

Current transformers type JGF are used in high voltage switchgear within the 245-550 kV range. They transform high current into standardised, equivalent values for meters, measuring and protection devices.

 

GENERAL DESCRIPTION

Current transformers type JGF are used in high voltage switchgear within the 245-550 kV range. They transform high current into standardised, equivalent values for meters, measuring and protection devices.

The current transformer section is located in the pressure-resistant head housing. The current transformer cores are fitted in a protective core shell made of massive cast aluminium, which is connected short-circuit proof to the bushing. The secondary outlets are passed through the SF6 /air bushing in the connection terminal box on the base construction of the insulator.

The current distribution along the insulator is optimised by a special layout of the control electrode inside the silicone composite insulator.

The housing components consist of helium-tight, corrosion-resistant cast aluminium. All housing components under pressure are individually typetested according to applicable pressure vessel standards.

The SF6 gas density is monitored temperature-compensated by a gas density monitor with alarm contacts. The special design means the function of the gas density monitor can be checked without dismounting it.

A corrosion-resistant metal rupture disc, protected by a metal cover, located at the top of the head housing ensures safe pressure relief in case of error.

The generously designed terminal box is equipped with a cover that opens sidewards.

Pure SF6 gas is used for ambient temperatures up to -40°C. The transformer is filled with a mixed gas for lower ambient temperatures up to -60°C.

Advantages of
current transformers
  • High operating safety through optimal current distribution in the field-controlled bushing
     
  • Low weight and high creepage resistance through the use of composite insulators
     
  • High flexibility due to simple primary and secondary changeover
     
  • High operating safety through pressure relief with rupture disc

 

HIGHLIGHTS

Easy primary changeover

Easy
primary changeover
  • A clear and easy primary changeover with a ratio of 1:2 or 1:2:4 is available.
     
  • The primary changeover is adjusted with one metal plate at each side of the head only.
     
  • No need to dismount or move the primary connections during adjustment.

Excellent protection against moisture

Excellent protection
against moisture
  • The inner side of the instrument transformer is protected against moisture by means of special sealing rings.
     
  • All housings are designed with a drain-age area to protect the sealing surfaces of the housings against rain. This significantly reduces crevice corrosion.
     
  • The housing elements are connected with special stainless steel screws. They are designed in such a way that no humidity can enter the screw hole.

Installation-friendly terminal box

Installation-friendly
terminal box
  • The generously sized terminal box with a cover that can be opened sidewards, is secured with captive screws. It can accommodate terminal blocks, fuses, spark gaps and sealable covers.
     
  • The terminal box is equipped as standard with a blind flange. Cable glands can be installed on request.
     
  • The terminal box has a protected ventilation aperture to prevent condensation.

 

DESIGN

 

TECHNICAL DATA

current transformer type JGF

Type JGF     245 300 330 362 420 550
Standard     IEC / IEEE
Highest voltage for equipment   kV 245 300 330 363 420 550
Rated power-frequency withstand voltage   kV 460 460 460 575 630 680
Rated lightning impulse withstand voltage   kV 1050 1050 1175 1175 1425 1550
Frequency   Hz 50 / 60
Primary rated current   A   5000
Secondary rated current   A 1 / 5
Rated short-time thermal current [Ith]   kA / 3s ≤ 80
Rated dynamic current [Idyn]   kA ≤ 200
Accuracy class     0.1-3; P; PR; PX; TPS; TPX; TPY; TPZ
Max. number of CT cores     8
Nominal operating / transport overpressure (20°C)   bar 4 / 0.5
       
Type JGF 245 300 330 362 420 550
Height of unit* A mm 4197 4197 5370 5370 5700 6530
Height to primary terminal* B mm 3681 3681 4730 4730 5090 5890
Depth of unit including terminal box C mm 845 845 1088 1088 1088 1088
Depth of unit base D mm 749 749 1088 1088 1088 1088
Width of unit base E mm 436 436 1075 1075 1075 1075
Distance between screw holes at base F mm 600 600 900 900 900 900
Min. creepage distance*   mm 6700 7500 8250 9050 10500 13750
Gross weight, approx.*   kg 670 670 - - 1130 1200
Gas weight, approx.*     38 38 - - 47 50

*with standard composite silicone insulator, creepage distance 25 mm/kV