portfolio single project
portfolio single project
portfolio single project
Previous

ECOTAP® VPD® III

The compact class for distribution transformers

ECOTAP® VPD® is the solution for all operators who have to maintain voltage in a defined and stable band in public, industrial and private distribution grids. Compact and able to be standardized, with a large control bandwidth even in fine steps, for autonomous, automatic voltage regulation and a communication interface: ECOTAP® VPD® is a highly economical solution while maintenance-free over the service life of the transformer. More and more operators are therefore introducing the voltage regulating distribution transformer in to their strategic network planning. It is also perfectly suited for grid-code-compliant connection of wind or solar parks.

APPLICATION

  VPD® III 30 A - 24 kV - 9 positions VPD® III 30 A - 36 / 40.5 kV - 9 positions VPD® III 30 A - 40.5 kV - 17 positions VPD® III 100 A - 36 / 40.5 kV - 9 positions VPD® III 100 A - 40.5 kV - 17 positions
Distribution networks recommended recommended   recommended  
Industrial supply     recommended   recommended
PV (utility scale)   recommended   recommended  
Wind turbine       recommended  
Small hydro   recommended   recommended  
Battery storage   recommended   recommended  

TECHNICAL DATA

  VPD® III 30 A - 24 kV - 9 positions VPD® III 30 A - 36 / 40.5 kV - 9 positions VPD® III 30 A - 40.5 kV - 17 positions VPD® III 100 A - 36 / 40.5 kV - 9 positions VPD® III 100 A - 40.5 kV - 17 positions
Max. rated through-current Irm 30 A 30 A 30 A 100 A 100 A
Highest voltage of equipment Um 24 kV 36 / 40.5 kV 40.5 kV 36 / 40.5 kV 40.5 kV
Max. rated step voltage Uirm 550 V 825 V 550 V 825 V 550 V
Max. number of operating positions 9 9 17 9 17
Rated frequency     50 Hz / 60 Hz    
Max. number of tap-change operations     500.000    

 

Motor-drive unit
Runtime per tap-change operation approx. 420 ms
Shortest gap between tap-change operations 3 s
Permissible ambient temperature during operation -25 °C ... +70 °C
Protection class IP54
Installation site Indoors, outdoors

 

Control unit
Permitted voltage range 100...240 VAC, 50/60 Hz
Note: Measured voltage is supply voltage  
Power consumption Max. 345 VA
Internal fuse (F1) Micro-fuse, 6,3x32 mm, min. 250 V, T4A
Permissible ambient temperature during operation Continuous operation: -25 °C...+50 °C
Brieflly (maximum of 2 h per day): -25 °C...+70 °C
Protection class IP30
Installation site Indoors, also suited to outdoor use in separate housing


Share